Changes compared to DinamoConfig 1.31
With DinamoConfig 1.32, you can request an analysis of the clock (synchronization between TM44s and TM-Hs). For now, this check is located behind the Master/Slave check that you can perform if you choose All-TMxx. A prerequisite is that the firmware of your TM44s is at least 1.21 and your TM-Hs is 5.21
The TM44/TM-H slave can report 4 states:
- Clock OK
- No Clock (occurs, for example, if the clock bus is short-circuited or interrupted)
- Bad Clock (means the clock is very poor, e.g., only 1 wire connected; Dinamo will barely function. Also occurs if the clock polarity is reversed)
- Degraded Clock (means the clock signal is getting through but shows timing errors; Dinamo will likely function, but possibly with unclear issues. This may indicate poor cables or errors with terminating resistors)
The TM44 master can report 2 states:
- Clock OK
- No Clock (occurs, for example, if the clock bus is short-circuited)
The TM-H master will always report clock-ok because it cannot perform a hardware check. When using a combination of TM44s and TM-Hs, it is strongly recommended to always choose a TM44 as the master.